Wednesday, June 17, 2009

Installation tips for Taco Venturi Tees

1)Venturi Fittings should be installed on the return side. Where the bypass requires additional flow, place the Venturi Fitting on the supply side. For maximum flow through the bypass, use two Venturi Fittings (one on the return side and one on the supply side).
2) Make sure that the arrows on the Taco Venturi Fittings are pointing in the proper direction for return or supply installation.
3) The Venturi fitting should always be installed with the Venturi marking between the by-pass supply and return lines.

Taco Tees and Venturi Fittings can be found at www.supplyhouse.com